                                    Quinta Ace cascade systems can be divided into three main groups:%u2022 Two to seven boilers in a linear configuration, wall-mounted (30 %u2013 115kW only)*%u2022 Two to eight boilers in a linear configuration, mounted on a free-standing frame (30 %u2013 115kW up to seven boilers, 135 %u2013 160kW up to 8 boilers)%u2022 Three to ten boilers in a back-to-back configuration, mounted on a free-standing frameThe boiler side of the cascade systems is sized to 20%u00b0C. The low loss header is based on 20/11%u00b0C.* Please note that the QA135 and QA160 are not suitable for wall hung cascade kits.Pumps Product codeQuinta Ace 30Quinta Ace 45Quinta Ace 55Quinta Ace 65Quinta Ace 90Quinta Ace 115Quinta Ace 135Quinta Ace 160UPM25/70 [130mm] Modulation pump for Quinta Ace 30 [c/w power + modulation cable]S101614UPML25/105 [130mm]Modulation pump for Quinta Ace 90 [c/w power + modulation cable]7608398UPMXL25-105 Auto [180mm] Modulation pump for Quinta Ace 135 [c/w power + modulation cable]7637223Key Description 135, 160Flue gas outlet connection %u00d8 100mmAir supply connection %u00d8 150mmSiphon connection 32mmFlow connection 1%u00bc\Return connection 1%u00bc\Gas connection 1\Quinta Ace 135%u201316058 Gas boilers
                                